AUT-SIGA-HRS
Detalhes
Specifications | |
70 foot (21.3 meter) spacing | |
15° F (9° C)/min rate-of-rise/135° F (57° C) ft. and 135° F (57 ° C) fixed temperature type | |
Intelligent detector c/w integral microprocessor | |
Non-volatile memory | |
Automatic device mappin | |
Electronic addressing | |
Identification of defective detectors | |
Twin RED/GREEN status LEDs | |
Standard, relay, fault isolator, and audible mounting bases | |
Designed and manufactured to ISO 9001 standards | |
Heat Sensing Element | Fixed & Temperature/ Rate-of-Rise |
Alarm Point | Alarms at 135ºF (57ºC) Ambient or Temp. increase above 15ºF (9ºC) per min |
UL Listed Detector Spacing | 70 feet (21.3 meters) center to center spacing |
Operating and Storage Environment | Operating Temp: 32ºF to 100ºF (0ºC to 38ºC) Storage Temp: -4ºF to 140ºF (-20ºC to 60ºC) Humidity: 0 to 93% RH, Non-Condensing |
Operating Voltage | 15.2 to 19.95 Vdc (19 Vdc nominal) |
Operating Current | Quiescent: 45µA @ 19 V Alarm: 45µA @ 19V Emergency Stand-alone Alarm Mode: 18mA Pulse Current: 100 µA (100 msec) |
Construction & Finish | High Impact Engineering Polymer - White |
LED Operation | On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm; Both LEDs - Glow steady when in alarm (stand-alone) Compatible Remote Red LED (model SIGA-LED) Flashes when in alarm |
Address Requirements | Uses one device address |
Agency Listings | UL, ULC, MEA, CSFM |