Detector de Fumaça
AUT-SIGA2-PS
Detalhes
Specifications | ||
Operating voltage | 15.20 to 19.95 VDC | |
Current | Normal operating | 45 µA |
Alarm | 45 µA | |
Stand-alone alarm | 18.6 mA | |
Air velocity | 0 to 4,000 ft./min (0 to 20.32 m/s) | |
Wall mounting: distance from ceiling | 12 in. (305 mm) max. | |
Operating environment | Temperature | 32 to 120°F (0 to 49°C) |
Relative humidity | 0 to 93% noncondensing | |
Storage temperature | 4 to 140°F (−20 to 60°C) | |
Environmental compensation | Automatic |